المواصفات الفنية العائدة لمجموعة ال UPS |
Geneneral conditions for all items: |
Brand Name - ISO Certified-1 year warranty labor and spare parts. |
|
|
Item 1 |
UPS 1000 VA |
UPS rating |
1000VA / 900W (0.9 PF) or better |
Technology |
True-on-line double conversion with automatic by-pass and power factor correction |
Input voltage range |
150V to 270V or better |
Input frequency range |
45 to 65Hz or better |
Output voltage/output frequency |
230V, adjustable to 208/220/230/240, 50 Hz auto select or frequency converter mode |
Battery type |
Built in sealed lead acid batteries gas recombination type for 10 minutes at 65% load. |
Battery management |
Automatic weekly test |
Outputs connections |
3 IEC sockets at least |
Standard compliance |
Equipment must be designed and built in accordance with accepted engineering practice and applicable international UPS standards |
Communication port |
USB or RS232+ one mini terminal block for remote ON/OFF and emergency stop |
Software for monitoring and shutdown |
must be supplied with the UPS to control output and for local remote supervision of the UPS |
Indicators and display |
Display of measurements , access to control and set-up menus |
Test report |
From independent reputable laboratories (UL, TÜV, …) |
|
|
|
|
Item 2 |
UPS 2 KVA |
UPS rating |
2000VA / 1800W |
Technology |
True-on-line double conversion with automatic by-pass and power factor correction |
Input voltage range |
160V to 270V or better |
Input frequency range |
45 to 65Hz or better |
Output voltage, output frequency, |
230V, adjustable to 208/220/230/240, 50 Hz auto select or frequency converter mode |
Battery type |
Built in sealed lead acid batteries gas recombination type for 10 minutes at 65% load. |
Battery management |
Automatic weekly test |
Outputs connections |
6 IEC sockets at least |
Standard compliance |
Equipment must be designed and built in accordance with accepted engineering practice and applicable international UPS standards |
Communication port |
USB or RS232+ one mini terminal block for remote ON/OFF and emergency stop |
Software for monitoring and shutdown |
must be supplied with the UPS to control output and for local remote supervision of the UPS |
Indicators and display |
Display of measurements , access to control and set-up menus |
Test report |
From independent reputable laboratories (UL, TÜV, …) |
|
|
|
|
|
|
Item 3 |
UPS 4 KVA |
UPS rating |
4 KVA /3,6 KW (0.9 pf) or better |
Technology |
True-on-line double conversion with automatic by-pass and power factor correction |
Input voltage range |
Single phase, 150V to 270V or better |
Input frequency range |
45 to 65Hz or better |
Output voltage, |
220-230Volts, |
output frequency, |
50Hz |
output THDU, |
<2,5%, |
Efficiency |
>90%,on line mode |
Battery type |
Built in Sealed lead acid batteries gas recombination type for 8 minutes at 65% load. |
Battery management |
Automatic weekly test |
Outputs connections |
7 IEC sockets at least |
Standard compliance |
Equipment must be designed and built in accordance with accepted engineering practice and applicable international UPS standards |
IEC/EN 62040-3,IEC/EN 62040-1-1,… |
|
For certification : |
Noise |
< 55 dbA |
Communication port |
USB or RS232+ one mini terminal block for remote ON/OFF and emergency stop |
Software for monitoring and shutdown |
must be supplied with the UPS to control output and for local remote supervision of the UPS |
Indicators and display |
Display of measurements , access to control and set-up menus |
Test report |
From independent reputable laboratories (UL, TÜV,…) |
|
|
|
|
|
|
Item 4 |
UPS 7 KVA |
UPS rating |
7 KVA/4,8KW or better |
Technology |
True-on-line double conversion technology with automatic and maintenance by-pass |
Input voltage range |
Single phase ,170 to 260V at 100% rated output, without discharging the batteries , |
Input frequency range |
40 to 60Hz or better |
Input THDI |
<5% |
Efficiency |
> 90% at full rated load, on line mode |
Output voltage/output frequency |
230V/50 Hz |
Battery type |
Sealed lead acid batteries gas recombination type for 10 minutes autonomy at 65% load, mounted inside cabinets supplied by UPS manufacturer with DC circuit breaker. |
Overload |
120% for 60sec at least |
Cold start |
To be provided to allow UPS start-up on battery power |
Standard compliance |
Equipment must be designed and built in accordance with accepted engineering practice and applicable international UPS standards |
Communication port |
USB or RS232+voltage free contacts |
Software for monitoring and shutdown |
must be supplied with the UPS to control output and for local remote supervision of the UPS |
Devices included |
Built-in automatic by-pass, manual by-pass, hot swap for UPS and batteries, automatic battery tester |
Test report |
From independent reputable laboratories (UL, TÜV, …) |
|
|
|
|
|
|
Item 5 |
UPS 11 KVA |
UPS rating |
11 KVA/8 KW or better |
Technology |
True-on-line double conversion technology with automatic and maintenance by-pass |
Input voltage range |
Single phase ,170 to 260V at 100% rated output, without discharging the batteries , |
Input frequency range |
40 to 60Hz or better |
Input THDI |
<5% |
Efficiency |
> 90% at full rated load, on line mode |
Output voltage/output frequency |
230V/50 Hz |
Battery type |
Sealed lead acid batteries gas recombination type for 10 minutes autonomy at 65% load, mounted inside cabinets supplied by UPS manufacturer with DC circuit breaker. |
Overload |
120% for 60sec at least |
Cold start |
To be provided to allow UPS start-up on battery power |
Standard compliance |
Equipment must be designed and built in accordance with accepted engineering practice and applicable international UPS standards |
Communication port |
USB or RS232+voltage free contacts |
Software for monitoring and shutdown |
must be supplied with the UPS to control output and for local remote supervision of the UPS |
Devices included |
Built-in automatic by-pass, manual by-pass, hot swap for UPS and batteries, automatic battery tester |
Test report |
From independent reputable laboratories (UL, TÜV, …) |
|
|
Item 6 |
UPS 20 KVA |
UPS rating |
20KVA/16KW or better |
Technology |
True-on-line double conversion technology using PFC controller with automatic and maintenance by-pass .. |
Input voltage range |
Three phase, 210V to 475V (Ph-Ph) . |
|
Redundant power feed from 2 independent sources (Separate mains 2) |
Input frequency range |
40 to 60Hz |
Output voltage, frequency, |
380 V , 50Hz |
efficiency |
≥ 90% |
Battery type |
Standard backup time: Built in (or inside original cabinets) sealed lead acid batteries gas recombination type for 10 minutes at full load |
Long backup time: Additionnal External sealed lead acid batteries gas recombination type for 90 minutes backup time+steel rack for batteries +battery circuit breaker. |
Overload |
150% for 60 seconds |
Standard compliance |
Equipment must be designed and built in accordance with accepted engineering practice and applicable international UPS standards |
Communication port |
SNMP/Web communication card |
Emergency power -off EPO |
The system shall include a terminal bloc to receive emergency power-off order |
Indicators and display |
The system shall include a LED signaling panel unit and a multilingual graphical display: display of measurements, access to control and set-up menus and an event log to store information such as the number of transfers to battery power… |
|
|
|
|
Item 7 |
UPS 30 KVA |
UPS rating |
30KVA/24KW or better |
Technology |
True-on-line double conversion technology using PFC controller with automatic and maintenance by-pass .. |
Input voltage range |
Three phase, 210V to 475V (Ph-Ph) . |
|
Redundant power feed from 2 independent sources (Separate mains 2) |
Input frequency range |
40 to 60Hz |
Output voltage, frequency, |
380 V , 50Hz |
efficiency |
≥ 90% |
Battery type |
Standard backup time: Built in (or inside original cabinets) sealed lead acid batteries gas recombination type for 10 minutes at full load |
Long backup time: Additionnal External sealed lead acid batteries gas recombination type for 60 minutes backup time+steel rack for batteries +battery circuit breaker. |
Overload |
150% for 60 seconds |
Standard compliance |
Equipment must be designed and built in accordance with accepted engineering practice and applicable international UPS standards |
Communication port |
SNMP/Web communication card |
Emergency power -off EPO |
The system shall include a terminal bloc to receive emergency power-off order |
Indicators and display |
The system shall include a LED signaling panel unit and a multilingual graphical display: display of measurements, access to control and set-up menus and an event log to store information such as the number of transfers to battery power… |